Models |
I-7015 |
I-7015P |
M-7015 |
M-7015P |
Analog Input |
Channels |
6 |
Wiring |
2/3-wire |
Sensor Types |
Pt100, Pt1000, Ni120, Cu50, Cu100, Cu1000 |
Resolution |
16-bit |
Accuracy |
±0.05% of FSR |
Sampling Rate |
12 Hz (Total) |
Individual Channel Configuration |
Yes |
Overvoltage Protection |
120 VDC |
Open Wire Detection |
Yes |
3-wire RTD Lead Resistance Elimination |
- |
Yes |
- |
Yes |
Resistance Measurement |
3.2 kΩ Max. |
|
Models |
I-7015 |
I-7015P |
M-7015 |
M-7015P |
Communication |
Interface |
RS-485 |
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rate |
1200 to 115200 bps |
Protocol |
DCON |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display |
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
I/O LED Indicator |
- |
7-Segment LED Display |
- |
Isolation |
Intra-Module Isolation, Field-to-Logic |
3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
EFT (IEC 61000-4-4) |
±4 kV for Power Line |
Surge (IEC 61000-4-5) |
- |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumption |
1.1 W |
1.2 W |
1.1 W |
1.2 W |
Mechanical |
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 to +75°C |
Storage Temperature |
-40 to +85°C |
Humidity |
10 to 95% RH, Non-condensing |
|