Analog Input |
Channel |
8 |
Wiring |
5-channel differential and 3-channel single-ended |
Input Range |
+/-150 mV, +/-500 mV, +/-1 V , +/-5 V, +/-10 V
+/-20 mA , 0~20 mA, 4~20 mA (Jumper selectable) |
Resolution |
12/16-bit |
Accuracy |
Normal Mode |
0.1% |
Fast Mode |
0.5% |
Sampling Rate |
Normal Mode |
10 Hz |
Fast Mode |
60 Hz |
Input Impedance |
Voltage |
20 M (Differential) |
Currnet |
10 M (Single-ended) |
Common Voltage Protection |
+/-15 VDC |
Individual Channel Configuration |
- |
Overvoltage Protection |
120 VDC |
Relay Output |
Channel |
4 |
Type |
Power Relay (Form A) |
Contact Rating |
5 A @ 250 VAC
5 A @ 30 VDC |
Surge Strength |
3000 VDC |
Operate Time |
3 ms |
Release Time |
2 ms |
Mechanical Endurance |
2 × 107 ops. |
Electrical Endurance |
105 ops. |
Power-on Value |
Yes |
Safe Value |
Yes |
Communication |
Interface |
RS-485 |
Format |
N, 8, 1 (details) |
Baud Rate |
1200 ~ 115200bps |
Protocol |
DCON Modbus/RTU |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display |
System LED Indicator |
Yes, 1 LED as Power/Communication Indicator |
I/O LED Indicator |
- |
7-Segment LED Display |
Yes |
Isolation |
Intra-Module Isolation, Field-to-Logic |
2500 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
+/-4 kV |
EFT (IEC 61000-4-4) |
+/-4 kV |
Surge (IEC 61000-4-5) |
+/-3 kV |
Power |
Reverse Polarity Protection |
Yes |
Input Voltage Range |
10 ~ 30 VDC |
Consumption |
1.8 W |
Mechanical |
Dimensions (W x L x H) |
72 mm x 123 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 ~ +75°C |
Storage Temperature |
-40 ~ +85°C |
Humidity |
10 ~ 95% RH, Non-condensing |