Model |
M-7024U |
M-7024UD |
Analog Output |
Channels |
4 |
Current Output Wiring |
Source |
Range |
0 ~+5 VDC, ±5 VDC, 0 ~ +10 VDC, ±10 VDC, 0 ~ +20 mA, +4 ~ +20 mA |
Resolution |
16-bit |
Accuracy |
±0.02%% of FSR |
DA Output Response Time |
10 ms per channel |
Programmable Output Slope |
Voltage |
0.0625 ~ 512 V/Second |
Current |
0.125 ~ 1024 mA/Second |
Current Output Capacity |
1000 Ω |
Open Wire Detection |
Yes, for 4 ~ 20 mA only |
Short Circuit Protection |
Yes |
Power-on Value |
Yes, Programmable |
Safe Value |
Yes, Programmable |
Digital Input |
Channels |
4 |
Wet Contact |
ON Voltage Level |
+1 VDC Max. |
OFF Voltage Level |
+4 ~ 30 VDC |
Dry Contact |
ON Voltage Level |
Close to GND |
OFF Voltage Level |
Open |
Effective Distance
for Dry Contact |
500 M Max. |
Counters |
Max. Count |
65535 (16-bit) |
Max. Input Frequency |
100 Hz |
Min. Pulse Width |
5 ms |
Input Impedance |
- |
Overvoltage Protection |
+60 VDC |
Digital Output |
Output Channels |
4 |
Type |
Open Collector |
Sink/Source (NPN/PNP) |
Sink |
Load Voltage |
+3.5 VDC ~ +50 VDC |
Max. Load Current |
700 mA/Channel |
Overvoltage Protection |
60 VDC |
Overload Protection |
1.4 A (with short-circuit protection) |
Power-on Value |
Yes, Programmable |
Safe Value |
Yes, Programmable |
|
Model |
M-7024U |
M-7024UD |
Communication |
Interface |
RS-485 |
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rate |
1200 to 115200 bps |
Protocol |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display |
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
I/O LED Indicators |
- |
4 LEDs as Analog Input Fault Indicators
4 LEDs as Digital Input Indicators
4 LEDs as Digital Output Indicators |
7-Segment LED Display |
- |
Isolation |
Intra-module Isolation,
Field-to-Logic |
2.5 kVDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±8 kV Contact for each Terminal |
EFT (IEC 61000-4-4) |
±4 kV for Power Line |
Surge (IEC 61000-4-5) |
- |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumption |
4 W |
4.5 W |
Mechanical |
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 to +75°C |
Storage Temperature |
-40 to +85°C |
Humidity |
10 to 95% RH, Non-condensing |
|