BACnet/IP to Modbus TCP Gateway GW-5493



 產品型錄(PDF)

 GW-5493 is a fully configurable universal Modbus RTU to BACnet/IP gateway. The GW-5493 includes BACnet/IP Server and Modbus TCP Client which is used to make Modbus TCP devices accessible on a BACnet network. 
BACnet (Building Automation and Control Networking) protocol has been designed specifically to meet the communication needs of building automation and control systems for applications such as heating, ventilating, air-conditioning control…etc.
The GW-5493 contains a large number of BACnet objects (AI, AO, AV, BI, BO, BV, MSI, MSO, MSV) gives you flexibility in mapping Modbus RTU registers to any combination of BACnet objects. Multiple BIBBs (DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM, DS-COV-B…etc.) are supported. All the data transfer is configurable using a standard Web browser.
 



     產品應用   
‧Building Automation
‧Heating, Ventilating, and Air-conditioning Control
‧Lighting Control
‧Access Control
‧Fire Detection Systems



  
      特   色      

General Features

  • Quickly and Cost Effectively integrate networks
  • Provide PWR/Communication Status indication LED
  • Read/Write any standard Modbus register via BACnet
  • No Programming Required
  • Modbus register mapping configured via web interface

BACnet

  • Fully Compliant with BACnet/IP Server
  • Supports up to 200 objects each of types: Analog Input, Analog Output, Analog Value, Binary Input, Binary Output, Binary Value, Multi-State Input, Multi-State Output,
  • BIBB (BACnet Interoperability Building Blocks) Supported: DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DS-COV-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B, DM-UTC-B, DM-RD-B

Modbus TCP

  • Fully User Configurable Modbus TCP Client
  • Supports Modbus coils, input register, holding registers
  • Supports for Function Code 0x01, 0x02, 0x03, 0x04, 0x05, 0x06, 0x10, 0x0F
     硬體規格    
System
CPU
32-bit
SDRAM
64 MB
Flash
64 MB
EEPROM
16 KB
Communication Ports
COM1
RS-232 (RxD, TxD, and GND); Non-isolation
Ethernet
10/100Base-TX Ethernet Controller
Protocol
Modbus
Modbus TCP Client
BACnet
BACnet/IP Server
BACnet Objects
AI, AO, AV, BI, BO, BV, MSI, MSO, MSV (Maximum: 200 each)
BIBB Supported
DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DS-COV-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B, DM-UTC-B, DM-RD-B
Mechanical
Dimensions (W x L x H)
91mm x 132mm x 52mm
Installation
DIN-Rail
Environmental
Operating Temp.
-25 ~ +75 °C
Storage Temp.
-30 ~ +85 °C
Humidity
5 ~ 90% RH, non-condensing
Power
Input Range
+10 ~ +30 VDC
Isolation
1 kV
Consumption
4.8 W (0.2 A @ 24 VDC)