Model |
I-7051 |
I-7051D |
M-7051 |
M-7051D |
Communication |
Interface |
RS-485 |
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
Format |
(N, 8, 1), (N, 8, 2), (E, 8, 1), (O, 8, 1) |
Baud Rate |
1200 ~ 115200 bps |
Protocol |
DCON |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display |
System LED Indicator |
Yes, 1 LED as Power/Communication Indicator |
I/O LED Indicators |
- |
Yes, 16 LEDs as Digital Input Indicators |
- |
Yes, 16 LEDs as Digital Input Indicators |
7-Segment LED Display |
- |
Isolation |
Intra-Module Isolation, Field-to-Logic |
3750 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
±8 kV Air for Random Point |
EFT (IEC 61000-4-4) |
±4 kV for Power Line |
Surge (IEC 61000-4-5) |
±3 kV for Power Line |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
10 ~ 30 VDC |
Consumption |
0.3 W |
1.1 W |
0.3 W |
1.1 W |
Mechanical |
Dimensions (W x L x H) |
72 mm x 123 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 ~ +75°C |
Storage Temperature |
-40 ~ +85°C |
Humidity |
10 ~ 95% RH, Non-condensing |
|